C-MAC CURRENT METERING MODULE

FPA38-400
  • Transmitter for kW, 3-phase symmetrical load
  • Connection to 3-phase grid up to 3 x 500 VAC
  • Measures total power consumption (√3 x U x I x cos phi)
  • Build-in current transformer, choice of range up to 60A
  • Analog output 0-20 mA / 4-20 mA
  • Galvanical separation between in- and output
  • 400VAC

FPA38 measures the power consumption at 3-phase symmetrical loads, primary motors. From DIP-switches the actual measuring range is selected between 0-3,46 kW and up to 0-41,6 kW at 3-400 VAC supply, corresponding to 0-20/4-20 mA at the measuring output. If possible 0-10 V measuring output is available too.

The supply voltage for the module is 24 VDC, and the 3 voltage-phases is connected to the respectively terminals. The current is measured by taking one of the current phases L! through the build-in current transformer, see further in the manual. 

Dimensions: 90 x 35 x 57 mm

Mastervarenr. FPA38-400
Mastervare Yes