Til Menu  
 

Programmable converter PMR10

  • Temperature inputs from RTD or thermocouple sensors
  • Potentiometer or variable resistor inputs
  • Sensor supply for NPN, PNP, NAMUR and analogue inputs
  • Analogue or pulse outputs
  • Galvanic separation, supply - input - output
  • DC supply or AC supply voltages up to 400 VAC
  • Made in accordance with the CE and EMC regulations

PMR10 is a multirange converter / isolation amplifier with temperature, resistance, pulse and analogue inputs and current, voltage, pulse or relay outputs.
The unit has a number of programmable input functions:

Temperature monitoring with 3-wire RTD sensors Pt100, Pt500; Pt1000, Ni100, Ni500 and Ni1000, including sensor cable monitoring.
Temperature monitoring with thermocouple sensors type J (Fe-CuNi), type K (NiCr-Ni), type R (Pt13%Rh-Pt), type S (Pt10%Rh-Pt), type T (Cu-CuNi), type B (Pt30%Rh-Pt6% Rh), type N (Nicrosil-Nisil) or type E (NiCr-CuNi).
When the unit is programmed for thermocouple sensor, you can select between internal Cold Junction Compensation and external CJC-box, which gives a higher accuracy. No matter which type of temperature sensor is used, the unit will compensate for the unlinearity of the sensor.

Potentiometer monitoring. If this function is selected, the output signal will indicate the actual position of the potentiometer, independent of the total value of the potentiometer.
Resistor monitoring. With resistor monitoring the output signal is an expression of the actual value of the resistor, compared with the programmed metering range.

Speed monitoring with programmable inputs from NPN, PNP orNAMURsensors, including supply voltage for the sensor.

Input signals from analogue transducers, including supply voltage for the transducer.

You can select between 2 different output configurations:

Type A is supplied with analogue current output, programmable between 0 and 20mAand analogue voltage output, programmable between -10 and +10 V.

Type B has the same outputs as type A, but in addition it is also supplied with pulse output, programmable to a maximum frequency of 10 kHz.

The unit is supplied with 2 trimming potentiometers, which can be used to fine-adjust the metering range, if the unit is used with analogue outputs. In either case the potentiometers can be disabled, if the adjustment possibility is not wanted.

If you want, you can order the unit with specified metering ranges, or you can program it yourself, by means of the Cmac programming software for PC and a small interface to connect between the PC and the module.