c-mac.gif (1316 bytes)  Signal converter / monitoring relay type LV10

Non-programmable signal converter / monitoring relay
Voltage input; current, voltage or relay output
Built-in exitation supply for transducer
Galvanic separation, supply - input - output
DC supply or AC supply voltages up to 230 VAC
Made in accordance with the CE and EMC regulations

 

lc10.jpg (7913 bytes)

The signal converters type LV10 convert a standard or non-standard analogue voltage input signal to a standard analogue output signal, selectable between 0-20 mA, 4-20 mA, 0-10 V or 2-10 V, and because all units have galvanic isolation between suppy, input and output, a safe and effective isolation between the input signals and the equipment, which is connected to the output of the converters, is ensured.

All connections to the converter module are placed on one terminal block, and therefore it is possible to install 2 independent converters in the same housing, thereby reducing the required space in the control panel, where the modules are installed. Optionally, the converters can be supplied with an input signal monitor with isolated transistor output. This output is only activated, if the input signal is within the specified metering range. If the converter is supplied with this monitor, only one converter can be installed in the housing.

The monitoring relays operate with the same input signals, but instead of having an analogue output signal, the modules are supplied with 2 relay outputs, where setpoints and relay functions are user adjustable. All monitoring relays have input signal monitor with transistor output, and only one module can be installed in each housing.

download datasheet (PDF-format)

Input connection examples:

Example 1:
External voltage source.

Example 2:
3-wire transducer with voltage output.
NOTE: Max. current output, pin 6 = 22 mA

Standard input ranges:
0 - 60 mV DC
0 - 10 VDC
0 - 250 VAC
0 - 500 VDC
0 - 500 VAC